Mechanism of the Disconnection of the Neutral Wire on the Measurement of the Three-phase Four-wire Electric Energy Meter
DIAO Rui-peng1,WANG Qiang1,LU Zhi-jun2
1. Qingdao Topscomm Communication Co., Ltd, Qingdao, Shandong 266109, China
2. Jin Hua Electric Power Design Institute CO., Ltd, Jinhua, Zhejiang 321001, China
Abstract:To solve the problem that the phase voltage measurement value is higher than actual value and the measurement error are caused when the neutral line is disconnected for the three-phase four-wire linear power meter. The changing law of the potential drift of the neutral terminal of the electric energy meter from the working process of the three-phase circuit is explored, and the cause of the three-phase four-wire electric energy meter in the neutral line disconnection is analyzed theoretically. The reason is verified to verify the accuracy of the theoretical analysis by simulation and experiment, and a method of neutral line current monitoring is proposed to identify the disconnection of the neutral line, which provides a sufficient theoretical basis for identify the disconnection of the neutral line and improving the accuracy of measurenment.
刁瑞朋,王强,卢志俊. 零线断接对三相四线电能表计量影响机理分析[J]. 计量学报, 2023, 44(5): 750-757.
DIAO Rui-peng,WANG Qiang,LU Zhi-jun. Mechanism of the Disconnection of the Neutral Wire on the Measurement of the Three-phase Four-wire Electric Energy Meter. Acta Metrologica Sinica, 2023, 44(5): 750-757.
Xie X, Wang L M, Zhang H Y, et al. Comparative Study on reliability prediction Standard for intelligent meter [J]. Acta Metrologica Sinica, 2019, 40(S1): 60-63.
Wang H R, Xu Y, Chang H. Effecting neutralpoint earthing on analysis of electric energy calcution [J]. Electric Switchgear, 2018, 56(6): 76-81.
Feng X T, Cui X, Ma W Z, et al. Double closed-loop control strategy of three-phase vienna rectifier based on unbalanced power grid [J]. Power System Technology, 2020, 45(5): 1976-1984.
Hou X Z, Liu X Z, Zheng K, et al. Technical prospect of a new generation smart meter in the ubiquitous power internet of things environment [J]. Electrical Measurement & Instrumentation, 2020, 57(9): 128-131.
Chen L J, Xing J, Wu D L, et al. Research on on-line monitoring method of multi-loop gateway electricity meter based on SVM [J]. Electrical Measurement & Instrumentation, 2021,58(8): 1-7.
Li Z N, Cai K, Lin R L. Analysis of the effects of wrong wiring on three-phase four-wire electric energy meter [J]. Metrology & Measurement Technique, 2019, 46(8): 69-72.
Wang W L. Analysis of the influence of inverse phase sequence on the measurement of three-phase active power [J]. Woodworking Machinery, 2017(4): 21-23, 26.
Fang H F, Sheng W X, Wang J L, et al. Research on the method for real-time onlinecontrol of three-phase unbalanced load indistribution area [J]. Chinese Journal of Electrical Engineering, 2015, 35(9): 2185-2194.
Peng C N, Luo R R, Wang X D. Research on a new generation of smart meter-technology supports ubiquitous power internet of things [J]. Electrical Measurement & Instrumentation, 2019, 56(15): 137-142.
Liu J B, Yang M, Li W Q, et al. Research on integrated decoupling network of EMS online testing system for electric energy meter [J]. Acta Metrologica Sinica, 2019, 40(S1): 136-139.
Ren X P, Li Z. The reason and prevention of the neutral line of three-phase four-wire electric energy meter [J]. Electric Test, 2018(15): 114-115.
Wang S Y, Liu J H. The influence of the metering for three-phase four-wire watt-hour meter not to connecting neutral line [J]. Electronics Quality, 2017(3): 14-16.
Zou L, Zhang C. Principle analysis and harm of unbalanced load of three-phase four-wire electric energy meter [J]. Practical Electronics, 2019(20): 86-87.
Analysis of common failures of smart electric energy meters and exploration of management strategies [J]. Information and communications, 2018(10): 281-282.