Multiple Inductive Current Dividers Calibration on Equipotential Working Condition
YANG Di1,LIN Jun1,ZHANG Jiangtao2,SHI Zhaomin2,PAN Xianlin2
1. School of Instrument Science and Electrical Engineering,Jilin University,Changchun,Jilin 130026,China
2. National Institute of Metrology,Beijing 100029,China
摘要提出了在等电位工作状态下校准多元感应分流器(multiple inductive current divider,MICD)的1种方法。在校准装置中加入由跟随器和电阻组成的I/V变换器,以使MICD各支路间的电流比例与其工作状态保持一致;用参考电流互感器(CT)提供独立的参考电流,以避免影响支路电流的比例关系。在20、55、400Hz及1kHz下对11支路MICD校准所得10:1电流比例的比值差合成标准不确定度优于0.2μA/A,相位差合成标准不确定度优于1.5μrad。
Abstract:A method for calibration of multiple inductive current dividers (MICD) is proposed.The I/V converter consisting of a voltage follower and a resistor is introduced in the calibration circuit, resulting in the same status for the current ratio of the branches of the MICD both in the calibration and the actual working condition.The MICD with 11 branches has been calibrated compared with an independent reference current provided by a reference current transformer (CT) used to avoid the influence on the current ratio of the branches.The MICD were calibrated at 20、 55、 400Hz and 1kHz.The results showed that the measurement standard uncertainty of ratio errors were better than 0.2μA/A and phase errors were better than 1.5μrad at the ratio of 10:1.
CHEN H B, YANG S N, CHEN L W, et al. Research on current transformer error testing technology based on field signal simulation technology [J]. Electrical Measurement & Instrumentation, 2021, 58(2): 133-138.
ZHANG Y F. Development of ac proportional technology [J]. Electrical Measurement & Instrumentation, 1983,20(4): 14-20.
LIU W, PAN X, JIN Z, et al. Design of the current comparator for measuring the current shunts at common ground [C] //CPEM 2016. Ottawa, ON, Canada, 2016.
YAN J, BAO J H, ZHOU S J, et al. Verification method of high current for standard current transformer [J]. Qinghai Electric Power, 2014, 33(2): 15-17.
JIN H B, WANG W H. Calibration and traceability system of value of a quantity of 400 Hz current transformer [J]. Aviation Metrology & Measurement Technology, 2001(2): 17-22.
BEAED G E. 100: 1 step up Amplifier-Aided Two-stage current transformer with small ratio error at 60 Hz. [J]. IEEE Transactions on Instrumentation & Measurement, 2007, 28(2): 146-152
ZHANG Y F. A calibration method for inductive current dividers [J] Acta Metrologica Sinica, 1980, 1(2): 132-141.
[20]
PAN X L, ZHANG J T. A Coaxial Time Constant Standard for the Determination of Phase Angle Errors of Current Shunts [J]. IEEE Transactions on Instrumentation & Measurement, 2013, 62(1): 199-204.
[23]
LIU W, PAN X, JIN Z, et al. Self-calibration of the current comparator with common ground [C] //CPEM 2016. Ottawa, ON, Canada, 2016.
ZHANG Z H, HE Q. Prospects of electromagnetic metrology in the 21st century [J]. Modern Measurement and Testing, 2009, 9(3): 3-6.
PAN X L, SHI Z M, ZHANG J T, et al. Research on key techniques of phase angle error measurement in establishment of the broadband power primary standard [J]. Measurement Technique, 2020(5): 35-39.
[14]
WANG Q, WANG H, XIANG Q. Design and calibration of inductive current Transformer [J]. Advanced Materials Research, 2013, 860-863: 2261-2265.
[18]
张佑峰. 感应分流器的一种校验方法 [J]. 计量学报, 1980, 1(2): 132-141.
PAN X L, ZHANG J T, SHI Z M, et al. A New Method to Compare Two Shunt-TVC Combinations at Common Ground [J]. Acta Metrologica sinica, 2020, 41(3): 317-321.
ZHANG X T, CHEN Q, DENG H F. Study of the phase deviation compensation on ac power measurement [J]. Electrical Measurement & Instrumentation, 2013, 50(1): 42-46.
XIONG K, JIANG C Y, LEI M, et al. Error characteristic study and experiment of inductive current divider [J]. Electrical Measurement & Instrumentation, 2017, 54(8): 80-84.
[24]
ZHANG J, GU Y, PAN X, et al. Determination of Equivalent Inductance of Current Shunts at Frequency Up to 200 kHz [J]. IEEE Transactions on Instrumentation and Measurement, 2013, 62(6): 140-144.
ZHANG Y F, ZHANG Z H. Using an“Increment Method” to Eliminate the Stray Error Sources and a Derived “Reference Increment Method” for Calibrating the Inductive Ratio Devices [J]. Acta Metrologica sinica, 1983, 4(3): 161-167
HE X B, WANG L R, JIN B, et al. Derive the proportional value of power frequency small current using an induction splitter [J]. Electrical Measurement & Instrumentation, 2013, 50(S1): 102-107.
[19]
ZHANG J T, PAN X L, LIN J, et al. A New Method for Measuring the Level Dependence of AC Shunt [J]. IEEE Transactions on Instrumentation & Measurement, 2010, 59(1): 140-144.